Maximum discharge rates for batteries are generally called "C" with units of hour^-1, though the units are often left off for some reason. For the purposes of
by dkbrk 6y ago
Maximum discharge rates for batteries are generally called "C" with units of hour^-1, though the units are often left off for some reason.
For the purposes of an installation such as this, C is essentially a constant, depending on factors such as the chemical and physical construction of the cells and thermal management system of the batteries. Given C and the maximum power output, you can calculate the actual energy capacity of the battery.
Describing capacity in terms of power rather than energy reflects its usage in actual practice. I doubt the C of the battery is higher than 1/hour, and peaker plants can be brought online on a timescale of 10 minutes or so. So if the grid has a shortfall in power, the relevant question is whether the battery has the power capacity to make up that difference. If it can, it should have the energy capacity to last until the rest of the grid brings online more supply (assuming it didn't start at a low state of charge).