Are you sure you're not confusing what you're describing with evaporative cooling? I don't think that the thermal delta between tap water and a warm room is eno
by gruez 6y ago
Are you sure you're not confusing what you're describing with evaporative cooling? I don't think that the thermal delta between tap water and a warm room is enough to justify the cost of filtered municipal tap water. For comparison, if the HVAC system simply fed the water into the radiators and dumped it, the max amount of heat you can capture is around 63J per gram of water (opportunistic assumptions of the water coming in at 5C and leaving at 20C). By comparison, if you evaporate the water, the latent heat of evaporation of water alone is 2257J per gram.
- myself248 6y agoI don't know for certain, but I didn't see any evaporators at the facility. Some places with high atmospheric humidity might have a hard time with evaporative cooling anyway. I think they might've been running a Freon loop with the condenser in tap water, to achieve higher thermal delta and just skip the enormous radiators and fans.
- gruez 6y ago>I don't know for certain, but I didn't see any evaporators at the facility. They're generally on top of the building, and they kinda look like generic air conditioning units. https://www.munters.com/en/munters/products/coolers--humidifiers/oasis-indirect-evaporative-coolers-iec/ https://www.munters.com/en/munters/products/coolers--humidif...