My favourite of that was when we grew from "some PCs plugged into extension leads from a floorbox" to four full racks of 2U servers, without ever upgrading the
by pjc50 7y ago
My favourite of that was when we grew from "some PCs plugged into extension leads from a floorbox" to four full racks of 2U servers, without ever upgrading the power distribution. Until someone noticed that one of the consumer-grade extension leads powering the whole setup had gone brown ...
Oh, and if there was a power cut you'd have to disconnect the racks and bring them back one at a time or the inrush current would trip the building breaker again.
- hinkley 7y agoI recall hearing years ago of someone modifying, I believe, the BIOS on a fileserver to spin up the hard drives one at a time so that the inrush current didn't cause brownouts (on the PSU or on the building circuit I don't recall)
- buzer 7y agoFacebook went a bit farther. https://engineering.fb.com/core-data/under-the-hood-facebook-s-cold-storage-system/ https://engineering.fb.com/core-data/under-the-hood-facebook... > The biggest change was allowing only one drive per tray to be powered on at a time. In fact, to ensure that a software bug doesn’t power all drives on by mistake and blow fuses in a data center, we updated the firmware in the drive controller to enforce this constraint. The machines could power up with no drives receiving any power whatsoever, leaving our software to then control their duty cycle.