Are all domestic buildings grounded this way in the US? Here (Sweden) I believe houses that aren’t far from transformers are only grounded at the nearest transf
by alkonaut 7y ago
Are all domestic buildings grounded this way in the US? Here (Sweden) I believe houses that aren’t far from transformers are only grounded at the nearest transformer (where power is transformed from 10kV 3-phase into 230/400V 3-phase+neutral for distribution to each house.
- serf 7y agoit's pretty common (pun unintended) , and usually preferred if you have any bigger electrical equipment like a garage shop.
- mindslight 7y agoYes, the neutral is tied to the earth at the transformer and also at every house on the transformer. This means that some return current technically runs through the earth back to the transformer. shrug
- mturmon 7y agoYes, all domestic buildings in the US have their own earth ground, and this is and has been required by the NEC (National Electrical Code). Often this is a thick, 8-foot long copper rod pounded into the ground not far from the electrical panel, connected to the panel by a ~1cm diameter copper cable. (There are other allowed methods, including using a similar copper electrode encased in concrete or in the building foundation.) It looks like this (which shows a galvanized-steel rod rather than the more canonical copper, and shows a further connection to a second ground rod, which is not required everywhere): http://www.wireyourownhouse.com/panel/images/grndrodexample.png http://www.wireyourownhouse.com/panel/images/grndrodexample.... Also, certain sub panels (e.g., in garages) will need their own separate earth ground, made the same way. This "grounding electrode" is in addition to a connection ("bond") to the domestic cold-water pipe, usually done where the pipe enters the building. (That pipe itself may be a hunk of copper buried in the ground.) The electrical bond to the water service is not a substitute for the dedicated grounding electrode mentioned above, it's to ensure that the plumbing does not become electrically charged.
- mattrp 7y agoAll except homes built many years ago where someone felt it was satisfactory to clamp a single wire to the water line. I’ve seen this numerous times. Not to mention the numerous instances of 20A breakers on 14awg. It’s simply amazing what one will find in some homes... like the person who clipped both ends of an extension cord to feed an outlet out of a junction box rather than spend $20 on home wiring. Or the person who literally covered a chiseled-out trench in plaster with painters tape to conceal wire. And on and on...
- bcrosby95 7y ago> where someone felt it was satisfactory to clamp a single wire to the water line. I’ve seen this numerous times. Our house was built in the 70's and that is what we used to have. After we upgraded our panel though we got not 1, but 2 grounding rods.
- mturmon 7y agoAccording to this thread [1], it was the 1978 code that required a dedicated grounding electrode. That's 40 years ago, but of course many houses have not been upgraded since then, and some localities might not have adopted the 1978 NEC until later. [1] https://forums.mikeholt.com/forum/active-forums/nec/86062-code-year-for-ground-rods?t=135832 https://forums.mikeholt.com/forum/active-forums/nec/86062-co...
- mattrp 7y ago2 is what I’ve installed in the houses I’ve renovated. It’s just not worth the risk to your electronics and home itself to cheap out on proper electrical in your house. Particularly if you’re one of those people with a 12 core 20tb dell r720 in the basement.
- chrisdhoover 7y agoAdding a ground to water pipe is a bad practice. With no hub rubber connectors it may not even work. It is also dangerous for any working the pipe