>I think fuseboard fuses are 32amp Most cables are 16A, so the outlets are 16A as well. Also UK uses 240V, not 230V. 32A circuit breakers would make the cables
by xxs 7y ago
>I think fuseboard fuses are 32amp
Most cables are 16A, so the outlets are 16A as well. Also UK uses 240V, not 230V. 32A circuit breakers would make the cables burn when overloaded.
- benj111 7y agoFlex cables might be 16amp, individual sockets are 16 amp though, so if you have more than one of those on a ring main... "Use a 30amp fuse or 32amp MCB for larger radial circuits, ring circuits up to 100m, cookers and electric showers up to 7200W" http://simplifydiy.com/electrical/basic-electrics/fuses http://simplifydiy.com/electrical/basic-electrics/fuses
- xxs 7y agonormal fuses (in the fusebox) still have to be 16A (B or C class), the main fuse can be anything 32-50A or even tri-phase 50A. >ring circuits up to 100m, cookers and electric showers up to 7200W Normally those tend to be 3phases. Of course it's possible to get over 16A on a single phase and a circuit breaker but that's quite a non-standard option. The issue is that if the fuse/circuit breaker is rated for 32A in a standard application (i.e. an outlet) the cables are likely to burn 1st.
- benj111 7y agoI think we might be getting our wires crossed :) I'm talking about the UK here, which I understood to be similar to the rest of Europe(?). That's a UK website and 3 phase isn't common here. I've just double checked my fuse box, and I have a 32 amp fuse for my socket ring main. Don't forget for a ring main the current is spread over 2 wires, so if theres 32amps power draw, theres only 16amp on each side of the ring.