Amazon AWS had a power failure, their backup generators failed
- the_70x 7y agoI wonder if they perform routine tests on their support infra: power, cooling, et al
- lithos 7y agoYes and frequently.
- aidanlister 7y agoWonder no more, the answer is: yes, obviously
- darkcha0s 7y agoNo, they just let it ride and hope nothing breaks.
- chasd00 7y agoI know you're being sarcastic but you're probably more right than you realize. Many many "redundant" systems turn out to not be so redundant when it counts. talk to some datacenter admins and you'll learn there's a lot more bailing wire and hope-for-the-best out there than you would think.
- ben509 7y agoSomeone is always signing off on routine tests. Same deal as those 50 point inspections your mechanic does: some things are easier to inspect than others, some people do a more thorough job than others, etc.
- lovetocode 7y agoSo dude is mad because he didn’t have a redundancy plan? You can take snapshots of EBS volumes which backs everything up to S3. They even tell you that EBS volumes can fail in the documentation. But blaming someone else is easier I guess...
- sheeshkebab 7y agoAWS need to add a button/option to ebs to have volumes be automatically backed up by aws itself. Without this few will do it or are even aware that it’s possible to do. It doesn’t help that ebs backup takes forever, especially initially.
- rad_gruchalski 7y agoAh, and the storm of "my AWS bill has skyrocketed, why is AWS doing this..." incoming in 1 week after such thing. No, thanks. RTFM.
- ReidZB 7y agoThey did add that: https://aws.amazon.com/backup/ https://aws.amazon.com/backup/
- ben509 7y agoHow do you do restore in those scenarios? You have a whole mess of snapshots of data that's in various stages of being wrong. I'd rather just put up with the agony of RDS to get a point in time restore and treat my instances' data as volatile.
- inopinatus 7y agoIn followup, turns out they didn't even lose data as claimed. It was a case of either lying or incompetence. Hunt didn't like that and blocked me for calling it out.
- ti_ranger 7y ago> In followup, turns out they didn't even lose data as claimed. Link?
- joncrane 7y agoIs there a source for this other than an angry Twitter user?
- random_visitor 7y agoI came across this news article: https://www.theregister.co.uk/2019/09/04/aws_power_outage_data_loss/ https://www.theregister.co.uk/2019/09/04/aws_power_outage_da... The headline sounded so clickbaity that I ignored it before seeing this thread
- hexteria 7y agoThe Register often uses snarky or tongue-in-cheek headlines, I like it tbh
- j2bax 7y agoHere is what Amazon shared via my support panel after the outage. [01:30 PM PDT] At 4:33 AM PDT one of ten data centers in one of the six Availability Zones in the US-EAST-1 Region saw a failure of utility power. Our backup generators came online immediately but began failing at around 6:00 AM PDT. This impacted 7.5% of EC2 instances and EBS volumes in the Availability Zone. Power was fully restored to the impacted data center at 7:45 AM PDT. By 10:45 AM PDT, all but 1% of instances had been recovered, and by 12:30 PM PDT only 0.5% of instances remained impaired. Since the beginning of the impact, we have been working to recover the remaining instances and volumes. A small number of remaining instances and volumes are hosted on hardware which was adversely affected by the loss of power. We continue to work to recover all affected instances and volumes and will be communicating to the remaining impacted customers via the Personal Health Dashboard. For immediate recovery, we recommend replacing any remaining affected instances or volumes if possible.
- skywhopper 7y agoThis seems to be getting slightly overblown in that thread. To be clear, this impacted one datacenter out of ten that make up one availability zone out of six in AWS’s us-east-1 region. So we are talking 2-3% at most of that region’s capacity was impacted. I haven’t seen a report yet on exactly why their generator failed, but from what I’ve heard, the power failed, and the backup generator kicked in and ran fine for over an hour, but then it failed. This sort of thing sucks to deal with but it’s also inevitable. Of their hundreds of datacenters, a mechanical failure is going to happen occasionally no matter how good their maintenance plans are. So the key when using cloud services like AWS is to plan for the possibility of failure. EBS expects an annual failure rate of 0.1%. So one out of a thousand EBS volumes will fail in a given year. If you operate at the scale of thousands of servers in AWS, you see this sort of thing all the time. Luckily, EBS also makes it trivial to take volume snapshots which are stored in S3, which has much much higher reliability and durability. So if you have data in EBS that needs to be kept safe, take regular snapshots. Here’s a doc that explains how you can set up scheduled, auto-rotated snapshots: https://docs.aws.amazon.com/AWSEC2/latest/UserGuide/snapshot-lifecycle.html https://docs.aws.amazon.com/AWSEC2/latest/UserGuide/snapshot...
- staticvar 7y agoDo you have a source detailing this issue in us-east-1? I don't see a recent post-event summary from AWS mentioning us-east-1 https://aws.amazon.com/premiumsupport/technology/pes/ https://aws.amazon.com/premiumsupport/technology/pes/
- j2bax 7y agoHere is what they said in my support panel. This event made for a fairly tense Saturday morning for my development team and I. [01:30 PM PDT] At 4:33 AM PDT one of ten data centers in one of the six Availability Zones in the US-EAST-1 Region saw a failure of utility power. Our backup generators came online immediately but began failing at around 6:00 AM PDT. This impacted 7.5% of EC2 instances and EBS volumes in the Availability Zone. Power was fully restored to the impacted data center at 7:45 AM PDT. By 10:45 AM PDT, all but 1% of instances had been recovered, and by 12:30 PM PDT only 0.5% of instances remained impaired. Since the beginning of the impact, we have been working to recover the remaining instances and volumes. A small number of remaining instances and volumes are hosted on hardware which was adversely affected by the loss of power. We continue to work to recover all affected instances and volumes and will be communicating to the remaining impacted customers via the Personal Health Dashboard. For immediate recovery, we recommend replacing any remaining affected instances or volumes if possible.
- carlsborg 7y agoThis conclusion "The cloud is just a .. blah blah blah" is weak: Amazon offers isolated availability zones within each region to mitigate this risk at the system level, it gives you the ability to take EBS snapshots that you can backup on S3 (with 11 9s of durability), and scaling features you just will not find on "just another computer." And you are meant to architect to this with multi-AZ designs. It's managed infrastructure not some miraculous alternative universe where probabilities do not apply to you. From the docs: "Amazon EBS volumes are designed for an annual failure rate (AFR) of between 0.1% - 0.2% ..."
- vectorEQ 7y agothe conclusion is weak but true. people do tend to forget the cloud is also a bunch of computers, and they might fail. however, it's not an argument to avoid cloud entirely, and in that sense its weak as an argument against cloud.
- earth2mars 7y agoexactly. remember, everything fails, all the time. https://thenextweb.com/2008/04/04/werner-vogels-everything-fails-all-the-time/ https://thenextweb.com/2008/04/04/werner-vogels-everything-f...
- philwelch 7y agoAgreed. If the cloud is somebody else's computer, I'm glad to let it be a computer that belongs to an extremely specialized and demanding company that focuses on providing that computer to me as a service.
- staticvar 7y agoThis tweet might be in response to the AWS Post event summary from August 23, 2019: > We’d like to give you some additional information about the service disruption that occurred in the Tokyo (AP-NORTHEAST-1) Region on August 23, 2019. Beginning at 12:36 PM JST, a small percentage of EC2 servers in a single Availability Zone in the Tokyo (AP-NORTHEAST-1) Region shut down due to overheating. https://aws.amazon.com/message/56489/ https://aws.amazon.com/message/56489/
- joncrane 7y agoBut the guy's tweet specifically mentions Reston (Virginia). This is in the vicinity of us-east-1. By the way, I'm pretty sure none of the actual AWS datacenters are in Reston proper. They are in Ashburn and other more sparse suburbs. Source: I live in the DC area and regularly visit Reston and Herndon. There are large AWS offices in Herndon but not so many datacenters. Real estate in Reston is pretty expensive.
- jsjohnst 7y ago> By the way, I'm pretty sure none of the actual AWS datacenters are in Reston proper. Pretty sure you are right. The physical AWS data centers I know of in Reston area are: 4 DCs on Smith Switch Rd in Ashburn, VA 2 DCs (IAD54 and IAD67) elsewhere in Ashburn, VA 3 DCs on West Severn Way in Sterling, VA 3 DCs on Dulles Summit Ct in Sterling, VA 2 DCs on Prologis Dr in Sterling, VA 2 DCs on Relocation Dr in Sterling, VA 2 DCs (IAD69 and IAD76) elsewhere in Sterling, VA 1 DC in South Riding, VA 4 DCs on Westfax Drive in Chantilly, VA 3 DCs on Mason King Ct in Manassas, VA 2 DCs elsewhere in Manassas, VA
- darkcha0s 7y agoThis just sounds like a bad architected solution, nothing else. The same problems that can happen in your own datacenter can happen in the cloud; it's just not your responsibility to fix it. If you lack that knowledge as an architect, rethink your title.
- empath75 7y agoNot only should you be architecting your app to survive an az going down you should be planning on an entire region going down and maybe even an entire cloud provider. It’s annoying when amazon has outages but they have local outages all the time and they give you all the tools you need to handle them.
- sgt101 7y agomoney money money though - all that time and effort (and fees) doesn't help you to lowball the next contract, cross your fingers and hope not to get caught out!
- rdxm 7y agoOK, it's 2019, almost 2020. Proper consumption of public cloud resources in a fashion that protects from individual Regional/AZ failures is common knowledge. How does a post like this make it onto HN?
- Polyisoprene 7y agoScary that AWS can’t restore EBS volumes properly after a power failure. Snapshot are not a solution to this in a live system.
- Quarrel 7y agoIf you lose power mid-write to an HDD, of course you can lose data. This guy sounds like if he'd self hosted he'd be complaining about an HDD failure. It happens- you need to design around it. Luckily, EBS volumes, snapshots and AZs make all of this pretty straight forward.
- Polyisoprene 7y agoData, sure. Lose the volume, no.
- cthalupa 7y agoIn my 15 years of experience as a sysadmin and architect, hard drives are far and above the most frequent hardware casualty of power failures. The EBS documentation states that there's an expected AFR of 1 to 2 per thousand volumes, so you should plan accordingly. Replicate any data that will cause harm to your business if lost to other sources. Keep backups.
- deleted 7y ago[deleted]
- notyourday 7y agoHe is just having a temper tantrum. Everything can fail and everything does fail. There was an outage a few years ago in a well known colo/ip/managed services provider where the feeder line from the power company failed, the ATS flipped to the backup power which had a limited run time. And, due to one of those 1/1000 events that should never happen (because that ATS should flip maybe 5-6 times a year) it fused to the new position. And it happened in a place where the DC operator would cut off the service on the second line to ensure they can safely work on removing the affected ATS. So the redundant power lines + backup power did not work. If you happened to be in that specific area of the building and happened to know building engineers and data center engineers and power company engineers you would have had heard what actually happened. Otherwise you just got "Imminent power failure" notification. Hopefully you knew that it means you want to shutdown all your workloads remotely and send someone you have on call who can reach the data center in 10-15 minutes to physically disconnect your PDUs from the incoming lines just in case someone messed up when they play at fixing the power so you don't blow 10-30% of your PDUs. That's the reality of the life in a data center. So yeah, either accept that stuff like this happens or build for stuff like this happening. Engineering around physical problems in the cloud environment is far easier than in the data center environment.
- acdha 7y agoI’ve seen at least 3 variations of the problem you mention, where power failover caused protracted downtime requiring rush delivery of niche replacement hardware. (That last is big: I’ve seen 8-figure enterprise hardware spends down for a week because it requires flying someone in to fix it, whereas AWS/Google has 24x7 staffing along with redundancy). Anyone thinking this doesn’t happen with private data centers is either very green or selectively excusing problems.
- serkanh 7y agoAlthough this was not reported on the status dashboard, this also affected elasticcache as well.It was acknowledged by the rep on the phone and via email issue got resolved. We weren't able start/reboot any redis instances on us-east-1a so had to launch on us-east-1c.
- nerdbaggy 7y agoI remember somebody on here writing out how when they worked at AWS they wrote custom firmware for their generators to get max performance.
- MichaelApproved 7y agoI couldn't find the HN post but I found an article that talks about firmware mods they do. https://www.datacenterknowledge.com/archives/2017/04/07/how-amazon-prevents-data-center-outages-like-deltas-150m-meltdown https://www.datacenterknowledge.com/archives/2017/04/07/how-... > The piece of technology Amazon designed to avoid this type of outage is the firmware that decides what electrical switchgear should do when a data center loses utility power. Typical vendor firmware prioritizes preventing damage to expensive backup generators over preventing a full data center outage, according to Hamilton. Amazon (and probably most other large-scale data center operators) prefers risking the loss of a sub-$1 million piece of equipment rather than risking widespread application downtime. > When everything happens as expected during a utility outage (which is the case most of the time), the switchgear waits a few seconds in case utility power comes back (also the most common scenario) and if it doesn’t, the switchgear fires up generators, while the data center runs on energy stored by UPS systems. Once the generators are stabilized, the switchgear makes them the primary source of power to the IT systems. > Last year’s Delta data center outage was attributed to switchgear “locking out” the generators at the airline’s facility in Atlanta. That’s what most switchgear is designed to do when it senses a major voltage anomaly either in the data center or on the incoming utility feed. Plugging a live generator into a shorted circuit will usually fry the generator, and switchgear locks generators out to avoid that.
- nerdbaggy 7y agoThat’s it thanks!
- generatorguy 7y agoDiesel generators at Hospitals and diesel motors running pumps for fire suppression systems are normally set up to keep running closer to the line of risking damage to the generator and engine.
- jrace 7y agoI think the real complaint is: >>Then it took them four days to figure this out and tell us about it.
- whoisjuan 7y agoI mean what did he expect? A 5 min resolution? 4 days sounds like a very reasonable investigation time to figure out why something complex failed.
- stickydink 7y agoI must have missed something entirely, did this all happen before the weekend? Where is the 4 days coming from? Amazon's RSS feed hit our Slack on Saturday morning with an explanation that the power had gone out and the backup generators failed. Is there some post mortem that just came out? >>We want to give you more information on progress at this point, and what we know about the event. At 4:33 AM PDT one of 10 datacenters in one of the 6 Availability Zones in the US-EAST-1 Region saw a failure of utility power. Backup generators came online immediately, but for reasons we are still investigating, began quickly failing at around 6:00 AM PDT. This resulted in 7.5% of all instances in that Availability Zone failing by 6:10 AM PDT. Over the last few hours we have recovered most...
- xxxpupugo 7y agoEBS is persistent right? I mean the failure of backup is not a surprise. Entropy is just everywhere.
- therealx 7y agoIs there a reason it often seems like backup generators fail? Is it that we don't hear the success stories of all the times they don't fail? Just due to not being tested often?
- dsr_ 7y agoIf you were buying datacenter space instead of cloud resources, you would expect each datacenter to report to you quarterly that they had run their backup generator tests and fixed any problems that occurred. You would also expect to be told in advance about network maintenance and other foreseeable service issues. Cloud vendors, of course, get to hide all that from you until something goes wrong.
- extrapickles 7y agoYes, you don’t hear the hundred or two times they start correctly, as they typically are tested quarterly to monthly. A good test is where you island the datacenter (run it only off the generators) so you can also make sure all the switchgear works.
- toast0 7y agoWe generally only hear about the failures, but it's also a tricky thing to test. Simple setups won't put load on the generator during the periodic tests, which can result in outages if the generator will start, but can't run the load for whatever reason (ex: mechanical problems, or load size grew beyond capacity). More complicated setups may be able to switch the load to the generator, but not switch back to utility fast enough in case the generator under test fails during the test. The transfer switches themselves are prone to failures and hard to make redundant. It seems that it's pretty hard to get this right from the beginning too, every large datacenter ends up learning this again after they have a sequence of power incidents. That said, successful switch to generator for 1 hour and then generator failure is not a terrible outcome; if there was a notification, that's enough time to evacuate critical systems (assuming you have a plan).
- dgritsko 7y agomLab was affected by this, and based on their own status page it looks like some volumes are permanently unrecoverable: https://status.mlab.com/ https://status.mlab.com/
- ReidZB 7y agoI can confirm that. We had a single-AZ RDS instance whose underlying storage (a "magnetic" EBS volume) unrecoverably failed, according to AWS. It had to be restored from a backup. Fortunately, "point-in-time recovery" meant there was very little data loss, just some downtime. (Not that data loss or downtime mattered for this instance, which was just used for internal testing.) Power-up is very stressful for hard drives, so it's not too surprising that some failed when the power turned back on. EBS does offer spinning rust storage options, so maybe mLab was using those for some of those failed volumes. I don't know if the same is true for SSDs or not.
- linsomniac 7y agoWe had a similar problem at our hosting facility last winter during that "Ice Vortex" storm that was all over the news. The facilities guys had been very proud of never having a power outage, I've had servers with them for 15 years now. The morning of the worst of the storm, we completely lose access to all services at that facility. Super unusual, everything we have there is redundant. So I do some minor investigation, and get on the horn to them. They were being super cagey. "Hey, we lost all access to our systems." "Ok, I'll open a ticket and we will investigate." "Uhhh. It feels like it's a big problem with the data center, are you guys having problems or is it just us?" "I can't say anything more until we've completed an investigation." "I'm trying to decide if we need to start failing over to our DR site, or if I need to put chains on the truck to drive 50 miles to the data center in this storm. Is anyone else having problems? Are fire alarms going off?" "We have received multiple reports of problems." Power was back on in less than half an hour, but they still weren't saying anything for a few hours. Spent that time trying to figure out if we should shut everything down and ride it out, or if they were back in business. We had one system that suffered disk corruption, despite having a (according to the weekly testing) correctly operating BBU on the RAID. So what happened? It shouldn't have been possible, our cabinet was being fed by two lines from independent PDUs. Each PDU is fed by 2 independent UPSes (one shared between the two PDUs), each UPS fed by a dedicated generator. Should have required 3 failures to bring us down. They eventually reveal that they had had one of their UPSes down for weeks, waiting for replacement parts. The other two UPSes had independent failures (one was a controller board, one was battery related). They said they still did quarterly full load tests of the power systems, but reading between the lines I think they weren't testing these two UPSes because the other one was not there to back them up. Still, one power event in 15 years isn't too shabby.
- jgalentine007 7y agoI had a similar situation in the early 2000's at NTT/Verio in Sterling, VA. They lost power because someone dug through a utility line and introduced a ground a fault into their system. They switched to generators and then against protocol (basically human error) tried to force override a transfer switch onto their other utility which ended up killing the generators. Eventually the UPSs were all drained, but we had to shutdown servers long ahead of that because with no AC, they were overheating. People were taking servers out by pickup truck to stand them up at their other offices and data centers. 48 hours of pain.
- durpleDrank 7y agoIs this North Virginia AGAIN???? How ironic that a company named "Amazon" cannot keep it's servers up when ever there is rain. This has happened practically every time hurricane season appears. Obviously being a bit hard on them (for humor) but come on guys, get a giant umbrella or something.
- linsomniac 7y agoPeople tend to make a habit of treating AWS like a VPS provider, in my experience. And you can skate by on this for a while, but it really isn't designed for that. And that will, eventually, lead to pain and suffering. Sometimes instances just go out to lunch. Sometimes an AZ goes down. Chaos Monkey isn't just a good idea, it's required for reliable operation. But please, please, if you are going to treat AWS like a VPS, at least don't do it in us-east-1! It seems to have more outages. Our setup related to instances and EBS includes: At least 2 instances in different AZs, an ELB in front of them, a backup running at our hosting facility (though this could just be a different AWS zone, or different provider), and DNS with full-paper-path health checks that switch DNS over to the colo servers if any component of the primary fails.
- ksec 7y agoForgive me, What may be a stupid question. As far as I can tell, the number of a Mechanical / Hardware Failure is far higher than Software. And it is always Power, UPS, Generator, BBU, Raid Card Failure etc. Why is it that we keep hearing failure in these segment? And it doesn't seems anything have been done? Are there any Innovation happening in this space?