The article isn't not really on point. A two-prong system still has an earthed neutral. The third prong is purely for redundancy. If neutral happens to be disco
by kazinator 7y ago
The article isn't not really on point. A two-prong system still has an earthed neutral. The third prong is purely for redundancy. If neutral happens to be disconnected, there is still a return path. It also protects against mixed up neutral and hot. If the chassis of a device is grounded to the third conductor, and that one is properly routed, then an inadvertent reverse wiring of hot/neutral is mitigated. A third conductor also makes possible ground fault detection: situations when a device is not returning all current through the neutral, because its safety ground has become energized.
How might a neutral end up disconnected? Not just by accident; for instance, someone would incorrectly wire a cold-side switch instead of hot-side (E.g. wall panel switch that controls an outlet) so that when the outlet is off, the neutral has been cut off, but hot is still live. In that situation, the third conductor would still be grounded. Nobody would mistakenly implement the switch on the ground line unless they didn't bother testing it, because the switch then wouldn't work; the ground line is implicitly protected from having switches accidentally planted on it by the fact that interrupting it does nothing, functionally.