There are a couple downsides here. When sizing a climate control system of any sort, it’s nice to size it such that, at full output, it will be just barely suf
by amluto 8y ago
There are a couple downsides here. When sizing a climate control system of any sort, it’s nice to size it such that, at full output, it will be just barely sufficient for the worst case usage. If you use it for demand response and time-of-use optimization, you either need to size for a worst-case day such that it’s still powerful enough when it’s switched off at expensive times or you need to store heat or cold for multiple days. Second, while a simple-ish hydronic system is great for heat, it’s less ideal for cooling. You need to make sure that a cooling system can remove sufficient water vapor to keep a comfortable humidity or you need a separate dehumidifier. (Ideally every new building in a humid climate would have independent dehumidification anyway, so this is not a show stopper.). It’s also important to avoid condensation in bad places — if you cool your floor or ceiling much below the dew point, you have a problem.