Yes it would, but part of that is that above a set pressure they can start venting. The idea is that an increase in pressure relative to ambient will cause a n
by jacquesm 8y ago
Yes it would, but part of that is that above a set pressure they can start venting.
The idea is that an increase in pressure relative to ambient will cause a needle (low flow) or disc (high flow) valve to open or close, pressure in the pipe higher than the desired delta will cause the valve to close and vice-versa.
The venting is a safety measure to protect downstream equipment in case of regulator failure (for instance, if it seizes too far open, or the seals are porous and the consumers are all not using gas which would slowly cause the pressure in the house side to rise to the same pressure as the feeder line), and normally this would be to let little bits of gas escape, but if the line pressure were high enough it would allow a constant stream of gas to escape from regulators that were 'borderline' or seized up. It could also cause the membrane under the spring to break, and that would let even more gas out through the seal between the tap stem and the regulator housing, and any consumers that were 'on' at the time would have to deal with the overpressure directly which they would not be designed for. They can handle a bit of overpressure but not for ever and not beyond certain set limits. Especially aluminum burner housings would simply burn up after some time.
In some lines there are burst plates as the final safety, those really should never go but when they do it is definitely a spectacle if there is an ignition source nearby. A burst place is a purposefully weakened structure that is bolted (with a seal) on top of a gasline so that when the pressure increases above the burst plate's rating the plate will rupture. This does not self reset for obvious reasons and will need an on-site technician to repair and would come with a serious investigation into what went wrong upstream.
There is also the opposite device, an emergency shutdown valve that automatically closes when the flow gets either too high or goes negative. The former to ensure that a ruptured pipe will not vent enormous quantities of explosive gas in to the atmosphere, the latter to avoid having an air/gas mixture in the lines.
Gas infrastructure is quite interesting, and very expensive to install and maintain.