The short version of the story is that grid electricity in Europe is produced by rotating the turbines 50 times a second and that's where the 50Hz AC electricit
by mrtksn 9y ago
The short version of the story is that grid electricity in Europe is produced by rotating the turbines 50 times a second and that's where the 50Hz AC electricity comes from.
Apparently to match the demand at given instance electricity plants rotate their turbines a bit faster or a bit slower instead of switching a complete plant on and off[edit: this is not exactly right, see the reply below], which results in slight deviations from the 50Hz standard but it is fine as long as it stays between the limits.
At the end of the day, as the demand increases and decreases, the average frequency would be 50Hz and engineers took advantage of that fact to create clocks that may not be accurate to the second but accurate on average. How do they do that? They count the change in the electricity and assume that 50 changes are exactly 1 second.
Unfortunately, due to political issues in the Balkans, the grid was undersupplied or oversupplied for a prolonged period and this created a deviation from the average of 50Hz and the clocks that depend on this average to be 50Hz also lost accuracy that currently amounts to 6 minutes.
- Slartie 9y ago> Apparently to match the demand at given instance electricity plants rotate their turbines a bit faster or a bit slower instead of switching a complete plant on and off, which results in slight deviations from the 50Hz standard but it is fine as long as it stays between the limits. This is slightly imprecise. It actually works the other way round: the demand is "communicated" through the network by slight changes in the frequency. This can be described best for the example of steam-based generators, as they are typical for the majority of coal/gas/oil/nuclear power plants. When demand for electricity grows, for example because a new factory is powered up, the turbines in the power plants are experiencing larger forces attempting to slow them down, starting with the power plant closest to the new factory. The speed (and thus the frequency) is constantly measured, and if it drops, the steam valve is opened just a tiny bit more to counteract the drop. If this is not possible because the power plant is already at maximum output, either other power plants have to take the load (and the electricity is then routed through the network to the factory) or additional power plants may have to be added to the network. The important thing is: the frequency change is a means of communication, it originates from demand changes, and because the entire network is kept in sync, it works to communicate demand changes across the entire network. Power plants providing energy to a sub-part of the entire network always attempt to run their turbines with the exact same speed of 50 rotations per second, which should ideally always conform to the frequency in all other sub-networks that a specific sub-network is attached to. If just one of these sub-networks does not perform its duty of re-establishing 50 Hertz by powering up their own plant output, the rest of the network must either channel enough power into this sub-network to allow its local generators to re-establish 50 rotations per second by taking some of the load off of them or - if that is not possible or decided against - must also deliberately drop their frequency (and thus the rotational speed of their generators) to match the sub-network that is deviating. The only alternative to this would be to drop off the deviating sub-network entirely, but that is usually only done in extreme cases of deviation.
- mrtksn 9y agoThanks for the correction, as more you read the more interesting it gets.
- Slartie 9y agoIt definitely does. And very interesting thoughts come up, especially when you add newer developments like non-rotational-mass-based power sources (solar power, batteries, stuff like that) into the mix. Because at the moment with the high number of traditional steam-powered generators, the rotating mass of the turbines and their inertia serve as a kind of buffer against sudden swings in electricity demand with an ultra-quick response time of "basically no time". As a second buffer stage we have the steam supplies in the plants, which can be quickly accessed just by opening a valve, thus the response time is non-zero, but still quite short. Now replace all those generators with some other power sources without those inherent balancing capabilities (that probably weren't explicitly built into them, but that just happen to be there because of their construction) and you'll get a network that is much more vulnerable to sudden changes on the demand side. Now, explicit mechanisms of storing energy in a way that can be accessed in literally zero time need to be introduced into the network, just to keep it stable and to provide other regulation mechanisms (of which a lot of them also have to be re-thought) with enough time to do their job. I wouldn't wonder if there were already plans for building large rotating masses with motors on them that are kept at network frequency, with the motors switching over to serve as generators when the frequency drops.
- Piskvorrr 9y agoWell...that's essentially the pumped-storage model, except it also takes tens of seconds to spool up: http://virtualniprohlidky.cez.cz/cez-dlouhe-strane-aj/ http://virtualniprohlidky.cez.cz/cez-dlouhe-strane-aj/
- beojan 9y ago> I wouldn't wonder if there were already plans for building large rotating masses with motors on them that are kept at network frequency, with the motors switching over to serve as generators when the frequency drops. Flywheels? Yes: https://en.wikipedia.org/wiki/Flywheel_energy_storage#Grid_energy_storage https://en.wikipedia.org/wiki/Flywheel_energy_storage#Grid_e....
- skgoa 9y agoWow, this explains why the clock on my gf's oven had deviated so much after years of keeping perfectly in sync with all the other clocks on our devices.
- fnl 9y agoYour answer doesn't seem to address the missing energy, said to be 113GWh, though - which seems the bigger issue according to the report.
- wglb 9y agoMinor nit—a generator is likely to not be rotating 50 times each second. Each rotation of the shaft could be generating multiple cycles depending on the wiring of the generator.
- tinus_hn 9y agoIf it worked like that, why would you base your clocks on these cycles?
- helb 9y agoIf anyone is interested in how the frequency and deviation changes are related (i was), i threw this quick-n-dirty chart together this morning: https://docs.google.com/spreadsheets/d/e/2PACX-1vR6ZsthgLiQA8QxylNK_Jem6WOnTnWutkTf-0AHVXGU87ITITaCU0Fmx48Og3--H0t_o4wL_I9TIku2/pubhtml# https://docs.google.com/spreadsheets/d/e/2PACX-1vR6ZsthgLiQA... It scrapes the swissgrid.ch page (with something like "curl | grep | sed > csv" in a loop), so the data is only as accurate/current as theirs… Edit: here's the actual sheet in case you want to "fork" it – https://docs.google.com/spreadsheets/d/1i9cLeKb5Eq1IoZFOUoOkRiVlxCG8iO-nL-fVIV6heqo/edit?usp=sharing https://docs.google.com/spreadsheets/d/1i9cLeKb5Eq1IoZFOUoOk...