13 ms·
The classic Bell System standard was that generators were started once a month and run for several hours. Once a year, each central office ran on emergency pow
by Animats 9y ago
The classic Bell System standard was that generators were started once a month and run for several hours. Once a year, each central office ran on emergency power for 24 hours, with external power shut off.
In the entire history of the Bell System prior to electronic switching, no central office was ever offline for more than 30 minutes for any reason other than a natural disaster.
- MandieD 9y agoOf course I've known that a DR plan isn't valid until you've tested it against your production environment, but I'd never heard that Bell System story before. It's inspirational - run 24 hours in emergency mode each year, with the normal way turned off/disconnected, don't just do failover/failback. Thanks for bringing it up!
- Animats 9y agoThey'd discover such things as a basement sump pump that wasn't on emergency power.