> It could be different in US, but in modern European installations the PE and N bars are separate In the US a single PE+N wire feeds into the building. All bu
by xenadu02 10y ago
> It could be different in US, but in modern European installations the PE and N bars are separate
In the US a single PE+N wire feeds into the building. All building wiring is separated as in Europe. They are tied together in only one location, usually wherever the main switch is.
Just like Europe, really old installs in the US don't have ground (PE). Some are retrofitted with ground like my house in SF. One thing people should never do is connect neutral to ground at a secondary point. It can be tempting when you don't have access to run a ground wire but creates a serious potential for safety problems. The way to handle that is to install a GFCI (RCD) plug and put a sticker on it stating "No equipment ground" - the outlets actually come with those stickers for that purpose :)
As far as I know in European systems where the building has separate PE+N feeds they are still bonded together, it just happens at the transformer. I could be wrong about that though!
- deleted 10y ago[deleted]
- zyx321 10y agoIn separate PE+N systems, the feeds join at a single master GFCI (typically one per distribution panel)