After searching around, it looks about average for a large data center. This link[1] estimates Google's data centers require between 50-100MW. 50MW is enough p
by burger_moon 11y ago
After searching around, it looks about average for a large data center. This link[1] estimates Google's data centers require between 50-100MW.
50MW is enough power to supply ~14k homes from different references I've seen.
I'm curious about what normal data centers use for backup power since natural gas and diesel generators don't get much bigger than 2MW. Or maybe they just don't have backup generators.
[1] http://www.datacenterknowledge.com/google-data-center-faq-part-2/ http://www.datacenterknowledge.com/google-data-center-faq-pa...
- neurotech1 11y agoThey do. Natural Gas fueled generators are practical at 50MW capacity. GE basically sells a 747 engine (CF6) driving a generator, known as the LMS6000 [0] https://en.wikipedia.org/wiki/General_Electric_LM6000 https://en.wikipedia.org/wiki/General_Electric_LM6000 [1] http://www.geaviation.com/marine/engines/military/lm6000/ http://www.geaviation.com/marine/engines/military/lm6000/
- mpnordland 11y agoThat's probably the most awesome thing I've heard tonight.
- burger_moon 11y agoI understand that gas turbines can produce that kind of power, in fact I used to work on some pretty large turbines and turbo generators in the 500-1000MW range. However they aren't used as backup generators where they have to be online in a minute. These are the types of generators I was referring to, https://powergen.gepower.com/products/reciprocating-engines/waukesha-vhp.html https://powergen.gepower.com/products/reciprocating-engines/...
- techdragon 11y agoMore batteries to get over the slower generator startup time, and likely quite a few smaller generators to do the best they can to keep the batteries going if the big generator is slower than expected to startup that day.
- ajaimk 11y agoThat is cool. Wonder what the efficiency of one of those will be.
- iSnow 11y ago40%, it's in the linked Wikipedia article.
- acveilleux 11y agoMaybe want to checkout engines from Wärtsilä. They have gas capable engines (50DF series, 50cm cylinder bore) with ratings up to 975kW/cylinders and up to 18 cylinders or 17MW per genset at 60hz. They're not the only player in that field. Fairbanks-Morse sells the Colt-Pielstick PC2.6 line with 750kW per cylinder at 600rpm and up to 16 cylinders for 11.5 MW @ 60hz. They also sell MAN 48/60 engines that go up to 21MW and MAN natural gas 51/60 G engines up to 18.5 MW.
- ctennis1 11y agoI ran a ~10MW capable facility for a while, we had 8 2MW Cummins gensets that would run in parallel. Extra units for redundancy as sometimes units would be offline for oil changes or other routine maintenance.